Item Description Material Apply Method
1 Conductor Bare copper wire Class 2 stranding
2 Insulation Flame retardant PVC Extruding
Core Identifcation    Green/yellow
Outer sheath marking (ink printing)  ZTT ELECTRIC CABLE 0.6/1kV nxn mm² CU 2018 IEC 60502-1 xxxxm

 

USING CHARACTERISTICS:

Min. temperature for fixing cable(°C) 0
Min. temperature for nominal operation(°C) -40
Min. bending radius after installed(mm) 10D
Cable design standard IEC 60502-1
Flame retardant IEC 60332-1
System frequency range (Hz) 49-61
Max. Continuous conductor temp.(°C) 90

 

DIMENSION DATA:

No.

Core No.
x Cross
Section

Nom.
Insulation
thick.

Approx. diam.
over insulation

Approx.
weight

Max. DC
resistance
of conductor at
20 °C

Current 
ratings in air
at 45 °

  (mm²) (mm) (mm) (kg/km) (Ω/km) (A)
16 1x70 1.4 12.8 698 0.268 242

CU/PVC 0.6/1KV 1X70