top of page

67) CU/PVC/IS/OAS/PVC/SWA/PVC 300/500V 2Px1
80) CU/PVC/IS/OAS/PVC/SWA/PVC 300/500V 4Tx1

 

 

ItemDescriptionMaterialApply Method
1ConductorBare copper wireClass 2 stranding
2InsulationPVCExtruding
3Drain WireBare Annealed CopperStranding
4Individual screenAluminum/mylar foilTaping
5Filler (if necessary)Flame retardant PP yarnStranding
6WrapperFlame retardant tapeTaping
7Drain WireBare Annealed CopperStranding
8Overall screenAluminum/mylar foilTaping
9Inner sheathPVCExtruding
10ArmorGalvanized steel wireStranding
11Outer sheathFlame retardant PVCExtruding
Core Identifcation   

Pair: Black, and White, each pair numbered                                                    
Triad: Black, White and Red, each triad numbered

Inner sheath colorBlack
Outter sheathBlack

 

USING CHARACTERISTICS:

Min. temperature for fixing cable(°C)0
Min. temperature for nominal operation(°C)-40
Min. bending radius after installed(mm)10D
Cabel design standardBS EN 50288-7
Flame retardantIEC 60332-1
System frequency range (Hz)49-61
Max. temperature for nominal operation (°C)70

 

DIMENSION DATA:

No.

Core
No.x
Cross
Section

Nom.
Insulation
thick.

Nom.
Individual
screen
thick.

Nom.
drain wire
are

Nom.
overall
screen
thick
Nom.
inner
sheath
thick.
Nom.
armor
wire
diam.
Nom.
outer
sheath
thick.
Approx.
diam.
over outer
sheath
Approx.
weight
Max. DC 
resistance of
Conducotr
at 20 °C
 (mm²)(mm)(mm)(mm²)(mm)(mm)(mm)(mm)(mm)(kg/km)(Ω/km)
672Px10.60.050.50.051.00.91.215.444818.1
804Tx10.60.050.50.051.01.251.320.083118.1

CU/PVC/IS/OAS/PVC/SWA/PVC

    Related Products

    bottom of page