Item | Description | Material | Apply Method |
1 | Conductor | Bare copper wire | Class 2 stranding |
2 | Insulation | PVC | Extruding |
3 | Filler (if necessary) | Flame retardant PP yarn | Stranding |
4 | Wrapper | Flame retardant tape | Taping |
5 | Inner sheath | PVC | Extruding |
6 | Armor | Galvanized steel wire | Stranding |
7 | Outer sheath | Flame retardant PVC | Extruding |
Core Identifcation | 3 cores: red, green, yellow, green/yellow | ||
Inner sheath color | Black | ||
Outer sheath color | Black |
USING CHARACTERISTICS:
Min. temperature for fixing cable(°C) | 0 |
Min. temperature for nominal operation(°C) | -40 |
Min. bending radius after installed(mm) | 12D |
Cable design standard | IEC 60502-1 |
Flame retardant | IEC 60332-1 |
System frequency range (Hz) | 49-61 |
Max. Continuous conductor temp.(°C) | 70 |
Max. Conductor temp. under short circuit(°C) | 160 |
DIMENSION DATA- 1:
No. | Core No.x | Nom. | Nom. | Nom. armor wire diam. | Nom. outer sheath thick. | Approx. diam. over outer sheath | Approx. weight | Max. DC resistance of conductor at 20 °C | Current |
---|---|---|---|---|---|---|---|---|---|
(mm²) | (mm) | (mm) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | (A) | |
46 | 3x2.5+E2.5 | 0.8 | 1.0 | 0.8 | 1.8 | 15.4 | 492 | 7.41 | 21 |