7) CU/XLPE/CWS/LSZH/AWA/LSZH 26/35kV 1x185/35
9) CU/XLPE/CWS/LSZH/AWA/LSZH 8.7/15kV 1x240/35
Item | Description | Material | Apply Method |
1 | Conductor | Bare copper wire | Class 2 stranding |
2 | Conductor screen | Semi-Conductive compound | |
3 | Insulation | XLPE compound | Triple extruding |
4 | Insulation screen | Semi-conductive compound | |
5 | Wrapper | Semi-conductive tape | Taping |
6 | Metallic screen | Bare copper wire | Stranding |
7 | Metallic tape | Bare copper wire | Taping |
9 | Wrapper | Flame retardant tape | Taping |
10 | Inner sheath | LSZH | Extruding |
11 | Armor | Aluminum wire | Stranding |
12 | Outer sheath | Flame retardant LSZH | Extruding |
Core Identification | Natural | ||
Inner sheath color | Black | ||
Outter sheath | Red |
USING CHARACTERISTICS:
Min. temperature for fixing cable(°C) | 0 |
Min. temperature for nominal operation(°C) | -40 |
Min. bending radius after installed(mm) | 15D |
Cable design standard | IEC 60502-2 |
Flame retardant | IEC 60332-1, IEC 60332-3-24(Cat. C) |
Low smoke | IEC 61034-2 |
Halogen free | IEC 60754-1 |
System frequency range (Hz) | 49-61 |
Max. Continuous conductor temp.(°C) | 90 |
Max. Conductor temp. under short circuit(°C) | 250 |
DIMENSION DATA:
No. | Core No.x | Nom. | Nom. metallic screen | Nom. inner | Nom. armor | Nom. | Approx. | Approx. | Max. DC |
---|---|---|---|---|---|---|---|---|---|
(mm²) | (mm) | (mm²) | (mm) | (mm) | (mm) | (mm) | (kg/km) | (Ω/km) | |
7 | 1x185/35 | 10.5 | 35 | 1.4 | 2.5 | 2.7 | 56.7 | 5153 | 0.0991 |
9 | 1x240/35 | 4.5 | 35 | 1.2 | 2.0 | 2.3 | 45.1 | 4391 | 0.0754 |
CURRENT RATING:
No. | Core No.x | Buried direct | In single-way duct | In air | ||||
---|---|---|---|---|---|---|---|---|
Trefoil | Flat spaced | Trefoil ducts | Flat touching ducts | Trefoil | Flat touching | Flat spaced | ||
mm² | A | A | A | A | A | A | A | |
(mm²) | ||||||||
7 | 1x185 | 406 | 410 | 387 | 391 | 543 | 550 | 637 |
9 | 1x240 | 469 | 470 | 447 | 453 | 641 | 647 | 745 |
Note:
- Maximum conductor temperature 90°C
- Ambient air temperature 30 °C
- Ground temperature 20 °C
- Depth of laying 0.8 m
- Thermal resistivity of soil 1,5 K.m/W
- Thermal resistivity of earthenware ducts 1,2 K.m/W
- De is overall diameter of cable
Correction factors for ambient air temperatures other than 30°C
Max. conductor temperature °C | Ambient air temperature °C | |||||||
20 | 25 | 35 | 40 | 45 | 50 | 55 | 60 | |
90 | 1.08 | 1.04 | 0.96 | 0.91 | 0.87 | 0.82 | 0.76 | 0.71 |
Correction factors for ambient ground temperatures other than 20°C
Max. conductor temperature °C | Ambient air temperature °C | |||||||
10 | 15 | 25 | 30 | 35 | 40 | 45 | 50 | |
90 | 1.07 | 1.04 | 0.96 | 0.93 | 0.89 | 0.85 | 0.80 | 0.76 |