top of page

2) CU/XLPE/IS/OAS/LSZH/SWA/LSZH 300/500V 12Px1

33) CU/XLPE/IS/OAS/LSZH/SWA/LSZH 300/500V 2Px1

54) CU/XLPE/IS/OAS/LSZH/SWA/LSZH 300/500V 8Px1

 

 

ItemDescriptionMaterialApply Method
1ConductorBare copper wireClass 2 stranding
2InsulationXLPEExtruding
3Drain WireBare Annealed CopperStranding
4Individual screenAluminum/mylar foilTaping
5Filler (if necessary)Flame retardant PP yarnStranding
6WrapperFlame retardant tapeTaping
7Drain WireBare Annealed CopperStranding
8Overall screenAluminum/mylar foilTaping
9Inner sheathLSZHExtruding
10ArmorGalvanized steel wireStranding
11Outer sheathFlame retardant LSZHExtruding
Core Identifcation   Pair: Black, and White, each pair numbered
Inner sheath colorB
Outer sheath colorBlack

 

USING CHARACTERISTICS:

Min. temperature for fixing cable(°C)0
Min. temperature for nominal operation(°C)-40
Min. bending radius after installed(mm)10D
Cable design standardBS EN 50288-7
Flame retardantIEC 60332-1, IEC 60332-3-24(Cat. C)
Low smokeIEC 61034-2
Halogen freeIEC 60754-1
System frequency range (Hz)49-61
Max. Continuous conductor temp.(°C)90

 

DIMENSION DATA:

No.

Core No.
x Cross
Section

Nom.
Insulation
thick.

Nom. 
Individual
screen
thick.

Nom.
drain wire 
area

Nom. 
overall 
screen
thick.

Nom.
drain
wire 
area

Nom. 
outer
sheath
thick.

Nom. 
inner 
sheath
thick.

Nom.
armor
sheath
thick.

Approx.
diam.
over outer
sheath

Approx.
weight

Max. DC 
resistance of
Conducotr
at 20 °C

 (mm²)(mm)(mm)(mm²)(mm)(mm²)(mm)(mm)(mm)(mm)(kg/km)(Ω/km)
212Px10.60.050.50.050.51.01.61.426.7142918.1
332Px10.60.050.50.050.51.00.91.215.444718.1
548Px10.60.050.50.050.51.01.61.423.6114518.1

CU/XLPE/IS/OAS/LSZH/SWA/LSZH

    Related Products