top of page

1) CU/XLPE/LSZH/SWA/LSZH 0.6/1kV           12x11.5+E1.5
27) CU/XLPE/LSZH/SWA/LSZH 0.6/1kV          2x11.5+E1.5
42) CU/XLPE/LSZH/SWA/LSZH 0.6/1kV          3x11.5+E1.5
52) CU/XLPE/LSZH/SWA/LSZH 0.6/1kV          5x11.5+E1.5
53) CU/XLPE/LSZH/SWA/LSZH 0.6/1kV          8x11.5+E1.5

 

 

ItemDescriptionMaterialApply Method
1ConductorBare copper wireClass 2 stranding
2InsulationXLPEExtruding
3Filler (if necessary)Flame retardant PP yarnStranding
4WrapperFlame retardant tapeTaping
5Inner sheathLSZHExtruding
6ArmorGalvanized steel wireStranding
7Outer sheathFlame retardant LSZHExtruding
Core Identifcation   Black with white number and green/yellow                                                 
Inner sheath colorBlack
Outer sheath colorBlack

 

USING CHARACTERISTICS:

Min. temperature for fixing cable(°C)0
Min. temperature for nominal operation(°C)-40
Min. bending radius after installed(mm)12D
Cable design standardIEC 60502-1
Flame retardantIEC 60332-1, IEC 60332-3-24(Cat. C)
Low smokeIEC 61034-2
Halogen freeIEC 60754-1
System frequency range (Hz)49-61
Max. Continuous conductor temp.(°C)90
Max. Conductor temp. under short circuit(°C)250

 

DIMENSION DATA:

No.

Core No.x
Cross Section

Nom.
Insulation
thick.

Nom.
inner
sheath
thick.

Nom.
armor
wire
diam.

Nom.
outer
sheath
thick.
Approx.
diam.
over
outer
sheath
Approx.
weight
Max. DC 
resistance of
Conducotr
at 20 °C
Current
ratings in
air at
45°C
 (mm²)(mm)(mm)(mm)(mm)(mm)(kg/km)(Ω/km)(A)
112x1.5+E1.50.7/0.71.01.251.820.790812.1/12.110
272x1.5+E1.507./0.71.00.81.813.135212.1/12.716
423x1.5+E1.50.7/0.71.00.81.813.939012.1/12.116
525x1.5+E1.50.7/0.71.00.81.815.648412.1/12.113
538x1.5+E1.50.7/0.71.01.251.818.875512.1/12.111

CU/XLPE/LSZH/SWA/LSZH 0.6/1KV 12X11.5+E1.5