top of page

28) CU/XLPE/LSZH/SWA/LSZH 0.6/1kV          2x10+E10
28) CU/XLPE/LSZH/SWA/LSZH 0.6/1kV          2x16+E16
28) CU/XLPE/LSZH/SWA/LSZH 0.6/1kV          2x25+E16
28) CU/XLPE/LSZH/SWA/LSZH 0.6/1kV          2x4+E4
28) CU/XLPE/LSZH/SWA/LSZH 0.6/1kV          3x120+E70
28) CU/XLPE/LSZH/SWA/LSZH 0.6/1kV          4x70+E35
28) CU/XLPE/LSZH/SWA/LSZH 0.6/1kV          4x95+E50

 

Item

DescriptionMaterialApply Method
1ConductorBare copper wireClass 2 stranding
2InsulationXLPEExtruding
3Filler (if necessary)Flame retardant PP yarnStranding
4WrapperFlame retardant tapeTaping
5Inner sheathLSZHExtruding
6ArmorGalvanized steel wireStranding
7Outer sheathFlame retardant LSZHExtruding
Core Identifcation   2+E core: red, light blue, green/yellow
3+E core: Red, green, yellow, green/yello
4+E core: Red, green, yellow, light blue, green/yellow                              
Inner sheath colorBlack
Outer sheath colorBlack

 

USING CHARACTERISTICS:

Min. temperature for fixing cable(°C)0
Min. temperature for nominal operation(°C)-40
Min. bending radius after installed(mm)12D
Cable design standardIEC 60502-1
Flame retardantIEC 60332-1, IEC 60332-3-24(Cat. C)
Low smokeIEC 61034-2
Halogen freeIEC 60754-1
System frequency range (Hz)49-61
Max. Continuous conductor temp.(°C)90
Max. Conductor temp. under short circuit(°C)250

 

DIMENSION DATA:

No.

Core No.x
Cross Section

Nom.
Insulation
thick.

Nom.
inner
sheath
thick.

Nom.
armor
wire
diam.

Nom.
outer
sheath
thick.
Approx.
diam.
over
outer
sheath
Approx.
weight
Max. DC 
resistance of
Conducotr
at 20 °C
Current
ratings in
air at
45°C
 (mm²)(mm)(mm)(mm)(mm)(mm)(kg/km)(Ω/km)(A)
282x10+E100.7/0.71.01.251.818.88871.83/1.8350
292x16+E1607./0.71.01.251.821.011461.15/1.1567
302x25+E160.9/0.71.01.61.824.015690.727/1.1589
322x4+E40.7/0.71.00.81.815.24934.61/4.6128
433x120+E701.2/1.11.22.02.446.064620.153/0.268237
504x70+E351.1/0.91.22.02.241.350540.268/0.524140
514x95+E501.1/1.01.22.02.445.964520.193/0.387170

CU/XLPE/LSZH/SWA/LSZH 0.6/1KV 2X10+E10