9) CU/XLPE/LSZH/SWA/LSZH 0.6/1kV 2x10+E10

 

 

ItemDescriptionMaterialApply Method
1ConductorBare copper wireClass 2 stranding
2InsulationXLPEExtruding
3Filler (if necessary)Flame retardant PP yarnStranding
4WrapperFlame retardant tapeTaping
5Inner sheathLSZHExtruding
6ArmorGalvanized steel wireStranding
7Outer sheathFlame retardant LSZHExtruding
Core Identifcation   Black with white number and green/yellow
Inner sheath colorBlack
Outer sheath colorBlack
Outer sheath marking (ink printing) ZTT ELECTRIC CABLE 0.6/1kV nxn mm² CU/XLPE/LSZH/SWA/LSZH 2018 IEC 60502-1 xxxxm

 

USING CHARACTERISTICS:

Min. temperature for fixing cable(°C)0
Min. temperature for nominal operation(°C)-40
Min. bending radius after installed(mm)12D
Cable design standardIEC 60502-1
Flame retardantIEC 60332-1, IEC 60332-3-24(Cat. C)
Low smokeIEC 61034-2
Halogen freeIEC 60754-1
System frequency range (Hz)49-61
Max. Continuous conductor temp.(°C)90
Max. Conductor temp. under short circuit(°C)250

 

DIMENSION DATA:

No.

Core No.
x Cross
Section

Nom.
Insulation
thick.

Nom.
inner 
sheath 
thick.

Nom. 
armor
wire 
diam.

Nom.
outer 
sheath 
thick.

Approx.
diam. 
over 
outer 
sheath

Approx. 
weight

Max. DC 
resistance 
of conductor 
at 20 °C

Current
ratings 
in air at 
45°C

 (mm²)(mm)(mm)(mm)(mm)(mm)(kg/km)(Ω/km)(A)
123x1.5+E1.50.7/0.71.00.81.813.939012.1/12.116
148x1.5+E1.50.7/0.71.01.251.818.875512.1/12.111

CU/XLPE/LSZH/SWA/LSZH 0.6/1KV 3X1.5+E1.5